ECO PID
PID Temperature Control Unit
High Resolution Sensitive PID control
TC (J,K,R,S,T Input Types) and RTD inputs
selectable by parameter
Low Power Consumption, Energy saving and
Environmentally Friendly with 2VA
Saving and Recovery of user parameters
Return to Factory Settings
3 Digits Process (PV) and 4 Digits Set (SV) display
Programmable ON-OFF, P, PI, PD, PID control forms
Adaptation of PID Coefficients to the system
with Self-Tune operation (Step ResponseTuning) and
Auto-Tune (limitcycling-tuning)
Selectable heating and cooling function
RS-485 Modbus (RTU) communication (Optional) Share :
TC (J,K,R,S,T Input Types) and RTD inputs
selectable by parameter
Low Power Consumption, Energy saving and
Environmentally Friendly with 2VA
Saving and Recovery of user parameters
Return to Factory Settings
3 Digits Process (PV) and 4 Digits Set (SV) display
Programmable ON-OFF, P, PI, PD, PID control forms
Adaptation of PID Coefficients to the system
with Self-Tune operation (Step ResponseTuning) and
Auto-Tune (limitcycling-tuning)
Selectable heating and cooling function
RS-485 Modbus (RTU) communication (Optional) Share :






Features | Descriptions |
Physical Features | |
Dimensions | 48 mm x 48 mm 86,5 mm |
Protection Class | IP65 at front, IP20 at rear |
Installation | Fixed Installation |
Storage / Operating Temperature | 0°C...50°C |
Storage / Operating Humidity | 90 % max. (None condensing) |
Electrical Features | |
Supply Voltage and Power | 100-240Vac 50/60Hz 115Vac (±%15) 50/60Hz 230Vac (±%15) 50/60Hz 24Vac/dc (±%15) 50/60Hz 24Vac (±%15) 50/60Hz 10-30Vdc |
Sensor Inputs | TC, RTDThermocouple (TC): J, K, R, S veT(IEC584.1)(ITS90) thermoresistance(RTD) PT-100 (IEC751)(ITS90) |
Optional Sensor Inputs | |
Scale | Fe CuNi -200°C,900°C NiCr Ni -200°C,1300°C Pt13%Rh 0°C,1700°C Pt10%Rh 0°C,1700°C Cu CuNi -200°C,400°C PT 100 -200°C,650°C PT 100 -199.9°C,650.0°C |
Accuracy | Thermocouple (TC):( ± 0.25% of full scale or ± 3ºC, which one is greater) ±1 digit max. Thermoresistance (RTD):( ± 0.25% of full scale or ± 2ºC, which one is greater) ±1 digit |
Output | |
Relay Output | Relay (5A@250Vac at Resistive Load) Relay (5A@250V ac at Resistive Load) (Alarm Output) |
SSR Output | Maximum 10 mA @ 12 Vdc |
Analogue Output | |
Optional Outputs | |
Control | |
Control Form | Programmable On / Off, P, PI, PD, and PID |
Reading Frequency | 10 readings per second |
Communication Protocols | |
Approvals | CE |